Rated voltage 10KV/35KV overhead insulated cable

Short Description:

  Application This product is a new type used for electricity supply on aerial power transmission lines.Which has been preferentially selected……


Product Detail

 

Application

This product is a new type used for electricity supply on aerial power transmission lines.Which has been preferentially selected as the 10KV and 35KV engineering transmission line for the construction and transformation of grid system.This series of products is appropriate for maintenance and security of lines,and the product with annealed copper core is applicable to the down lead of transformer.

Product features

(1) The rated voltage is 10KV、35KV;during having a short circuit(lasting less than 5 seconds), the maximum temperature:XLPE insulated cables is 250℃, HDPE insulated cables is 150℃;the permissible long time working temperature of conductor:relative to the PVC insulated and polythene insulated cable,it must be below 70℃, relative to the XLPE insulated and polythene insulated cable,it must be below 90℃;during the cable laying,the ambient temperature must be above -20℃.

(2) The permissible bending radius shall not be less than the diameter of the cylinder used in the cable bending test.

 

Type names and usable range

Type

Name

Usage range

JKYJ

Aerial cross-linking polyvinyl insulated copper core cable


To be fixedly laid in the air. When the product with annealed copper core is applied to the down lead of transformer,a definite distance shall be maintained between cables and trees.

JKTRYJ

Aerial cross-linking polyvinyl insulated annealed copper core cable

JKLYJ

Aerial cross-linking polyvinyl insulated aluminium core cable

JKLHYJ

Aerial cross-linking polyvinyl insulated aluminium alloy core cable

JKY

Aerial polyvinyl insulated copper core cable

JKTRY

Aerial polyvinyl insulated annealed copper core cable

JKLY

Aerial polyvinyl insulated aluminium core cable

JKLHY

Aerial  polyvinyl insulated aluminium alloy core cable

JKLYJ/Q

Aerial light cross-linking polyvinyl insulated aluminium core cable

 

To be fixedly laid in the air. A definite distance should be maintained between cables should be maintained between cables and trees.During power transimission,the cable can be allowed in contact with trees just for a short time.

JKLHYJ/Q

Aerial light cross-linking polyvinyl insulated aluminium alloy core cable

JKLY/Q

Aerial light polyvinyl insulated aluminium core cable

JKLHY/Q

Aerial light polyvinyl insulated aluminium alloy core cable

 

Manufacture range

Type

Number of cores

(mm2) Nominal cross area

10KV

35KV

JKYJ JKTRYJ
JKLYJ JKLHYJ

1

10-300

50-300

3

25-300

3+N(A)或3+N(B)

25-300

JKY JKTRY JKLY JKLHY

JKLYJ/Q JKLHYJ/Q JKLHY/Q

 

Aerial insulated cable of rated voltage

(mm2)
Nominal cross area oconductor

(mm)
Calculated diameter

(mm)
Thickness insulator

(kg/km) Appoximate weight

(mm2)
Nominal cross area conductor

(mm)
Calculated diameter

(kg/km) AW

JKYJ

JKLYJ

JKY

JKLY

JKYJ

JKLYJ

JKTRYJ

JKLHYJ

JKTRY

JKLHY

JKTRYJ

JKLHYJ

1×10

3.4

13

190

128

191

129

1×16

3.4

14

257

158

258

159

1×25

3.4

15

348

194

350

195

3×25

34

1053

585

1×35

3.4

16

450

234

451

235

3×35

36

1361

705

1×50

3.4

17

600

290

601

292

3×50

39

1814

878

1×70

3.4

19

800

366

801

368

3×70

43

2418

1108

1×95

3.4

20

1050

462

1052

464

3×95

47

3174

1396

1×120

3.4

22

1290

548

1293

550

3×120

50

3902

1656

1×150

3.4

23

1580

650

1581

652

3×150

54

4773

1965

1×185

3.4

25

1910

766

1913

768

3×185

58

5657

2315

1×240

3.4

27

2430

943

2431

946

3×240

63

7344

2852

1×300

3.4

29

2991

1134

2994

1137

3×300

68

9045

3430

 

10KV
Aerial insulated cable of rated voltage

35KV
Aerial insulated cable of rated voltage

(mm2)
Nominal cross area conductor

(mm)
Calculated diameter

(mm)
Thickness insulator

(kg/km) AW

(mm2)
Nominal cross area conductor

(mm)
Calculated diameter

(mm)
Thickness insulator

(kg/km) AW

JKLYJ/Q

JKLY/Q

JKYJ

JKLYJ

JKLHYJ/Q

JKLHY/Q

JKTRYJ

JKLHYJ

1×25

2.5

11.0

157

158

1×35

2.5

12.0

194

195

1×50

2.5

13.3

247

249

1×50

9.3

30

1044

734

1×70

2.5

15.0

326

327

1×70

9.3

32

1278

844

1×95

2.5

16.6

419

421

1×95

9.3

34

1553

946

1×120

2.5

18.0

502

504

1×120

9.3

35

1821

1078

1×150

2.5

19.6

600

604

1×150

9.3

37

2140

1212

1×185

2.5

21.2

712

715

1×185

9.3

38

2504

1359

1×240

2.5

23.4

885

889

1×240

9.3

40

3068

1580

1×300

2.5

25.6

1069

1071

1×300

9.3

43

3671

1814

 